  • Simple to install and operate
  • 3 m long stainless steel fluid filled bulb and capillary
  • Energy saving, line-sensing electronic control thermostat
  • Adjustable set point: -4 °C to 163 °C
  • Direct switching, maximum current 16 A, 230 VAC

View full description

Quick Find: 1485
Part Code: 404385-000

Weight: 3.00 Kg

This product is currently awaiting on stock arrival and due in soon.

This product is currently awaiting on stock arrival and due in soon.

Backorder now to secure your delivery or sign up to be notified when this product is back in stock.


Free Delivery Available*
£429.75 ex VAT
£515.70 inc VAT
£515.70 inc VAT
£429.75 ex VAT
Stock Available: 4 Units

Qty

Estimated delivery: 10 working days

Made To Order This is a made to order product and therefore cannot be returned or cancelled

This EEx d approved surface sensing thermostat provides temperature control for all nVent RAYCHEM BTV, QTVR, KTV, VPL and XTV heating cables in hazardous areas. The switching temperature range is –4°C to +163°C and is adjustable externally to the Ex enclosure by a dial mounted under a bolted-on cover and seal.

The switching current capacity is 22 A. It has a single pole change-over switch with volt-free contacts. Cable entry is through a single 3/4" NPT thread entry.

nVent RAYCHEM cable glands are available to suit nonarmoured and armoured cable. The 3 m long stainless steel fluid filled bulb and capillary give freedom to locate the enclosure remote from the bulb.

The bulb exposure range is –50°C to +215°C. The cast aluminium construction with stainless steel fittings gives a lightweight unit which can be pipe mounted using nVent RAYCHEM support brackets or surface mounted.

Technical specifications

Ambient temperature-40°C to 60°C
BrandnVent
Current22 A
Temperature adjustment−4 to 163 °C